CVE-2022-25622 Detail

Current Description

A vulnerability has been identified in SIMATIC CFU DIQ, SIMATIC CFU PA, SIMATIC ET 200pro IM154-8 PN/DP CPU, SIMATIC ET 200pro IM154-8F PN/DP CPU, SIMATIC ET 200pro IM154-8FX PN/DP CPU, SIMATIC ET 200S IM151-8 PN/DP CPU, SIMATIC ET 200S IM151-8F PN/DP CPU, SIMATIC ET200AL IM157-1 PN, SIMATIC ET200ecoPN, AI 8xRTD/TC, M12-L, SIMATIC ET200ecoPN, CM 4x IO-Link, M12-L, SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L, SIMATIC ET200ecoPN, CM 8x IO-Link, M12-L, SIMATIC ET200ecoPN, DI 16x24VDC, M12-L, SIMATIC ET200ecoPN, DI 8x24VDC, M12-L, SIMATIC ET200ecoPN, DIQ 16x24VDC/2A, M12-L, SIMATIC ET200ecoPN, DQ 8x24VDC/0,5A, M12-L, SIMATIC ET200ecoPN, DQ 8x24VDC/2A, M12-L, SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 MF HF, SIMATIC ET200SP IM155-6 PN HA (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/2 HF (incl. SIPLUS variants), SIMATIC ET200SP IM155-6 PN/3 HF (incl. SIPLUS variants), SIMATIC PN/MF Coupler, SIMATIC PN/PN Coupler, SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants), SIMATIC S7-300 CPU 314C-2 PN/DP, SIMATIC S7-300 CPU 315-2 PN/DP, SIMATIC S7-300 CPU 315F-2 PN/DP, SIMATIC S7-300 CPU 315T-3 PN/DP, SIMATIC S7-300 CPU 317-2 PN/DP, SIMATIC S7-300 CPU 317F-2 PN/DP, SIMATIC S7-300 CPU 317T-3 PN/DP, SIMATIC S7-300 CPU 317TF-3 PN/DP, SIMATIC S7-300 CPU 319-3 PN/DP, SIMATIC S7-300 CPU 319F-3 PN/DP, SIMATIC S7-400 CPU 412-2 PN V7, SIMATIC S7-400 CPU 414-3 PN/DP V7, SIMATIC S7-400 CPU 414F-3 PN/DP V7, SIMATIC S7-400 CPU 416-3 PN/DP V7, SIMATIC S7-400 CPU 416F-3 PN/DP V7, SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V10 CPU family (incl. SIPLUS variants), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants), SIMATIC TDC CP51M1, SIMATIC TDC CPU555, SIMATIC WinAC RTX 2010, SIMATIC WinAC RTX F 2010, SINAMICS DCM, SINAMICS G110M, SINAMICS G115D, SINAMICS G120 (incl. SIPLUS variants), SINAMICS G130, SINAMICS G150, SINAMICS S110, SINAMICS S120 (incl. SIPLUS variants), SINAMICS S150, SINAMICS S210, SINAMICS V90, SIPLUS ET 200S IM151-8 PN/DP CPU, SIPLUS ET 200S IM151-8F PN/DP CPU, SIPLUS HCS4200 CIM4210, SIPLUS HCS4200 CIM4210C, SIPLUS HCS4300 CIM4310, SIPLUS NET PN/PN Coupler, SIPLUS S7-300 CPU 314C-2 PN/DP, SIPLUS S7-300 CPU 315-2 PN/DP, SIPLUS S7-300 CPU 315F-2 PN/DP, SIPLUS S7-300 CPU 317-2 PN/DP, SIPLUS S7-300 CPU 317F-2 PN/DP, SIPLUS S7-400 CPU 414-3 PN/DP V7, SIPLUS S7-400 CPU 416-3 PN/DP V7. The PROFINET (PNIO) stack, when integrated with the Interniche IP stack, improperly handles internal resources for TCP segments where the minimum TCP-Header length is less than defined. This could allow an attacker to create a denial of service condition for TCP services on affected devices by sending specially crafted TCP segments.


View Analysis Description

Severity



CVSS 3.x Severity and Metrics:

NIST CVSS score
NIST: NVD
Base Score:  7.5 HIGH
Vector:  CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H

Nist CVSS score does not match with CNA score
CNA:  Siemens AG
Base Score:  5.3 MEDIUM
Vector:  CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L


NVD Analysts use publicly available information to associate vector strings and CVSS scores. We also display any CVSS information provided within the CVE List from the CNA.

Note: It is possible that the NVD CVSS may not match that of the CNA. The most common reason for this is that publicly available information does not provide sufficient detail or that information simply was not available at the time the CVSS vector string was assigned.

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to nvd@nist.gov.

Hyperlink Resource
https://cert-portal.siemens.com/productcert/pdf/ssa-446448.pdf Vendor Advisory 

Weakness Enumeration

CWE-ID CWE Name Source
CWE-400 Uncontrolled Resource Consumption cwe source acceptance level NIST   Contributor acceptance level Siemens AG  

Known Affected Software Configurations Switch to CPE 2.2

CPEs loading, please wait.

Denotes Vulnerable Software
Are we missing a CPE here? Please let us know.

Change History

14 change records found show changes

Quick Info

CVE Dictionary Entry:
CVE-2022-25622
NVD Published Date:
04/12/2022
NVD Last Modified:
07/11/2023
Source:
Siemens AG