Current Description

A vulnerability has been identified in SIMATIC ET 200SP Open Controller CPU 1515SP PC (All versions), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (All versions), SIMATIC S7-1200 CPU family (All versions >= V4.0), SIMATIC S7-1500 CPU family (All versions), SIMATIC S7-1500 Software Controller (All versions), SIMATIC S7-PLCSIM Advanced (All versions). An attacker in a Man-in-the-Middle position could potentially modify network traffic exchanged on port 102/tcp, due to certain properties in the calculation used for integrity protection. In order to exploit the vulnerability, an attacker must be able to perform a Man-in-the-Middle attack. The vulnerability could impact the integrity of the communication. No public exploitation of the vulnerability was known at the time of advisory publication.

Source:  MITRE
View Analysis Description

Severity



CVSS 3.x Severity and Metrics:

NIST CVSS score
NIST: NVD
Base Score: 5.9 MEDIUM
Vector:  CVSS:3.0/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to nvd@nist.gov.

Hyperlink Resource
https://cert-portal.siemens.com/productcert/pdf/ssa-232418.pdf Vendor Advisory
https://cert-portal.siemens.com/productcert/pdf/ssa-273799.pdf

Weakness Enumeration

CWE-ID CWE Name Source
CWE-284 Improper Access Control NIST  
CWE-327 Use of a Broken or Risky Cryptographic Algorithm Siemens AG  

Known Affected Software Configurations Switch to CPE 2.3

Configuration 1 ( hide )
 cpe:/o:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc_firmware
     Show Matching CPE(s)
Running on/with
 cpe:/h:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc:-
     Show Matching CPE(s)

Configuration 2 ( hide )
 cpe:/o:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc2_firmware
     Show Matching CPE(s)
Running on/with
 cpe:/h:siemens:simatic_et_200sp_open_controller_cpu_1515sp_pc2:-
     Show Matching CPE(s)

Configuration 3 ( hide )
 cpe:/o:siemens:simatic_s7-1200_cpu_1211c_firmware
     Show Matching CPE(s)
Up to (including)
4.0
Running on/with
 cpe:/h:siemens:simatic_s7-1200_cpu_1211c:-
     Show Matching CPE(s)

Configuration 4 ( hide )
 cpe:/o:siemens:simatic_s7-1200_cpu_1212c_firmware
     Show Matching CPE(s)
Up to (including)
4.0
Running on/with
 cpe:/h:siemens:simatic_s7-1200_cpu_1212c:-
     Show Matching CPE(s)

Configuration 5 ( hide )
 cpe:/o:siemens:simatic_s7-1200_cpu_1214c_firmware
     Show Matching CPE(s)
Up to (including)
4.0
Running on/with
 cpe:/h:siemens:simatic_s7-1200_cpu_1214c:-
     Show Matching CPE(s)

Configuration 6 ( hide )
 cpe:/o:siemens:simatic_s7-1200_cpu_1215c_firmware
     Show Matching CPE(s)
Up to (including)
4.0
Running on/with
 cpe:/h:siemens:simatic_s7-1200_cpu_1215c:-
     Show Matching CPE(s)

Configuration 7 ( hide )
 cpe:/o:siemens:simatic_s7-1200_cpu_1217c_firmware
     Show Matching CPE(s)
Up to (including)
4.0
Running on/with
 cpe:/h:siemens:simatic_s7-1200_cpu_1217c:-
     Show Matching CPE(s)

Configuration 8 ( hide )
 cpe:/o:siemens:simatic_s7-1500_cpu_1518_firmware
     Show Matching CPE(s)
Running on/with
 cpe:/h:siemens:simatic_s7-1500_cpu_1518:-
     Show Matching CPE(s)

Configuration 9 ( hide )
 cpe:/o:siemens:simatic_s7-1500_cpu_1511c_firmware
     Show Matching CPE(s)
Running on/with
 cpe:/h:siemens:simatic_s7-1500_cpu_1511c:-
     Show Matching CPE(s)

Configuration 10 ( hide )
 cpe:/o:siemens:simatic_s7-1500_cpu_1512c_firmware
     Show Matching CPE(s)
Running on/with
 cpe:/h:siemens:simatic_s7-1500_cpu_1512c:-
     Show Matching CPE(s)

Configuration 11 ( hide )
 cpe:/a:siemens:simatic_s7-1500
     Show Matching CPE(s)
 cpe:/a:siemens:simatic_s7-plcsim_advanced
     Show Matching CPE(s)


Change History

4 change records found - show changes

Quick Info

CVE Dictionary Entry:
CVE-2019-10929
NVD Published Date:
08/13/2019
NVD Last Modified:
10/09/2019