Search Results (Refine Search)
- Keyword (text search): cpe:2.3:h:rockwellautomation:controllogix_5560:-:*:*:*:*:*:*:*
- CPE Name Search: true
Vuln ID | Summary | CVSS Severity |
---|---|---|
CVE-2022-1161 |
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. Published: April 11, 2022; 4:15:18 PM -0400 |
V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2021-22681 |
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Published: March 03, 2021; 1:15:14 PM -0500 |
V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |