CVE-2023-27976 |
A CWE-668: Exposure of Resource to Wrong Sphere vulnerability exists that could cause remote code execution when a valid user visits a malicious link provided through the web endpoints. Affected Products: EcoStruxure Control Expert (V15.1 and above) Published: April 18, 2023; 1:15:07 PM -0400 |
V4.0:(not available) V3.1: 8.8 HIGH V2.0:(not available) |
CVE-2023-1548 |
A CWE-269: Improper Privilege Management vulnerability exists that could cause a local user to perform a denial of service through the console server service that is part of EcoStruxure Control Expert. Affected Products: EcoStruxure Control Expert (V15.1 and above) Published: April 18, 2023; 1:15:07 PM -0400 |
V4.0:(not available) V3.1: 5.5 MEDIUM V2.0:(not available) |
CVE-2022-45789 |
A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions) Published: January 31, 2023; 1:15:07 AM -0500 |
V4.0:(not available) V3.1: 9.8 CRITICAL V2.0:(not available) |
CVE-2022-45788 |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when a malicious project file is loaded onto the controller. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions), Modicon Momentum Unity M1E Processor - 171CBU* (All Versions), Modicon MC80 - BMKC80 (All Versions), Legacy Modicon Quantum - 140CPU65* and Premium CPUs - TSXP57* (All Versions) Published: January 30, 2023; 8:15:09 AM -0500 |
V4.0:(not available) V3.1: 9.8 CRITICAL V2.0:(not available) |
CVE-2022-37302 |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a crash of the Control Expert software when an incorrect project file is opened. Affected Products: EcoStruxure Control Expert(V15.1 HF001 and prior). Published: September 13, 2022; 6:15:10 AM -0400 |
V4.0:(not available) V3.1: 5.5 MEDIUM V2.0:(not available) |
CVE-2022-26507 |
A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer Published: April 14, 2022; 9:15:11 AM -0400 |
V4.0:(not available) V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2020-7560 |
A CWE-123: Write-what-where Condition vulnerability exists in EcoStruxure™ Control Expert (all versions) and Unity Pro (former name of EcoStruxure™ Control Expert) (all versions), that could cause a crash of the software or unexpected code execution when opening a malicious file in EcoStruxure™ Control Expert software. Published: December 10, 2020; 8:15:12 PM -0500 |
V4.0:(not available) V3.1: 8.6 HIGH V2.0: 6.8 MEDIUM |
CVE-2020-7559 |
A CWE-120: Buffer Copy without Checking Size of Input ('Classic Buffer Overflow') vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause a crash of the PLC simulator present in EcoStruxureª Control Expert software when receiving a specially crafted request over Modbus. Published: November 19, 2020; 5:15:14 PM -0500 |
V4.0:(not available) V3.1: 7.5 HIGH V2.0: 5.0 MEDIUM |
CVE-2020-7538 |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause a crash of the PLC simulator present in EcoStruxureª Control Expert software when receiving a specially crafted request over Modbus. Published: November 19, 2020; 5:15:14 PM -0500 |
V4.0:(not available) V3.1: 7.5 HIGH V2.0: 5.0 MEDIUM |
CVE-2020-28213 |
A CWE-494: Download of Code Without Integrity Check vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause unauthorized command execution when sending specially crafted requests over Modbus. Published: November 19, 2020; 5:15:13 PM -0500 |
V4.0:(not available) V3.1: 8.8 HIGH V2.0: 6.5 MEDIUM |
CVE-2020-28212 |
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause unauthorized command execution when a brute force attack is done over Modbus. Published: November 19, 2020; 5:15:13 PM -0500 |
V4.0:(not available) V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2020-28211 |
A CWE-863: Incorrect Authorization vulnerability exists in PLC Simulator on EcoStruxureª Control Expert (now Unity Pro) (all versions) that could cause bypass of authentication when overwriting memory using a debugger. Published: November 19, 2020; 5:15:13 PM -0500 |
V4.0:(not available) V3.1: 7.8 HIGH V2.0: 4.6 MEDIUM |