NIST has updated the NVD program announcement page with additional information regarding recent concerns and the temporary delays in enrichment efforts.
CVE-2022-2502 DetailDescriptionA vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function. Severity
CVSS 4.0 Severity and Metrics:
NVD Analysts use publicly available information to associate vector strings and CVSS scores. We also display any CVSS information provided within the CVE List from the CNA. Note: NVD Analysts have not published a CVSS score for this CVE at this time. NVD Analysts use publicly available information at the time of analysis to associate CVSS vector strings. References to Advisories, Solutions, and ToolsBy selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to nvd@nist.gov.
Weakness Enumeration
Known Affected Software Configurations Switch to CPE 2.2CPEs loading, please wait.
Denotes Vulnerable Software Quick InfoCVE Dictionary Entry:CVE-2022-2502 NVD Published Date: 07/26/2023 NVD Last Modified: 08/03/2023 Source: Hitachi ABB Power Grids |