Current Description
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
A vulnerability has been identified in the following Siemens industrial products: SIMATIC S7-200 Smart: All versions < V2.03.01, SIMATIC S7-400 PN V6: All versions < V6.0.6, SIMATIC S7-400 H V6: All versions < 6.0.8, SIMATIC S7-400 PN/DP V7: All versions, SIMATIC S7-410 V8: All versions, SIMATIC S7-300: All versions, SIMATIC S7-1200: All versions, SIMATIC S7-1500: All versions < 2.0, SIMATIC S7-1500 Software Controller: All versions < 2.0, SIMATIC WinAC RTX 2010 incl. F: All versions, SIMATIC ET 200AL: All versions, SIMATIC ET 200ecoPN: All versions, SIMATIC ET 200M: All versions, SIMATIC ET 200MP: All versions, SIMATIC ET 200pro: All versions, SIMATIC ET 200S: All versions, SIMATIC ET 200SP: All versions, DK Standard Ethernet Controller: All versions, EK-ERTEC 200P: All versions < V4.5, EK-ERTEC 200 PN IO: All versions, SIMOTION D: All versions < V5.1 HF1, SIMOTION C: All versions < V5.1 HF1, SIMOTION P: All versions < V5.1 HF1, SINAMICS DCM: All versions, SINAMICS DCP: All versions, SINAMICS G110M / G120(C/P/D) w. PN: All versions < V4.7 SP9 HF1, SINAMICS G130 and G150: All versions, SINAMICS S110 w. PN: All versions, SINAMICS S120: All versions, SINAMICS S150 V4.7 and V4.8: All versions, SINAMICS V90 w. PN: All versions, SINUMERIK 840D sl: All versions, SIMATIC Compact Field Unit: All versions, SIMATIC PN/PN Coupler: All versions, SIMOCODE pro V PROFINET: All versions, SIRIUS Soft starter 3RW44 PN: All versions. Specially crafted packets sent to port 161/UDP could cause a Denial-of-Service condition. The affected devices must be restarted manually.
Metrics
NVD enrichment efforts reference publicly available information to associate
vector strings. CVSS information contributed by other sources is also
displayed.
By selecting these links, you will be leaving NIST webspace.
We have provided these links to other web sites because they
may have information that would be of interest to you. No
inferences should be drawn on account of other sites being
referenced, or not, from this page. There may be other web
sites that are more appropriate for your purpose. NIST does
not necessarily endorse the views expressed, or concur with
the facts presented on these sites. Further, NIST does not
endorse any commercial products that may be mentioned on
these sites. Please address comments about this page to nvd@nist.gov.
A vulnerability has been identified in Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200, Development/Evaluation Kits for PROFINET IO: EK-ERTEC 200P, SIMATIC Compact Field Unit, SIMATIC ET200AL, SIMATIC ET200M (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN BA (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN HF (incl. SIPLUS variants), SIMATIC ET200MP IM155-5 PN ST (incl. SIPLUS variants), SIMATIC ET200S
Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually.
Added
CVSS V4.0
Siemens AG CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Added
CVSS V3.1
Siemens AG AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Added
Reference
Siemens AG https://cert-portal.siemens.com/productcert/html/ssa-141614.html [No types assigned]
Added
Reference
Siemens AG https://cert-portal.siemens.com/productcert/html/ssa-346262.html [No types assigned]
Added
Reference
Siemens AG https://cert-portal.siemens.com/productcert/html/ssa-546832.html [No types assigned]
A vulnerability has been identified in the following Siemens industrial products: SIMATIC S7-200 Smart: All versions < V2.03.01, SIMATIC S7-400 PN V6: All versions < V6.0.6, SIMATIC S7-400 H V6: All versions < 6.0.8, SIMATIC S7-400 PN/DP V7: All versions, SIMATIC S7-410 V8: All versions, SIMATIC S7-300: All versions, SIMATIC S7-1200: All versions, SIMATIC S7-1500: All versions < 2.0, SIMATIC S7-1500 Software Controller: All versions < 2.0, SIMATIC WinAC RTX 2010 incl. F: All versions, SIMATIC ET
A vulnerability has been identified in SIMATIC S7-200 Smart, SIMATIC S7-400 PN V6, SIMATIC S7-400 H V6, SIMATIC S7-400 PN/DP V7, SIMATIC S7-410 V8, SIMATIC S7-300, SIMATIC S7-1200, SIMATIC S7-1500, SIMATIC S7-1500 Software Controller, SIMATIC WinAC RTX 2010 incl. F, SIMATIC ET200AL, SIMATIC ET200ecoPN, SIMATIC ET200M, SIMATIC ET200MP, SIMATIC ET200pro, SIMATIC ET200S, SIMATIC ET200SP, Development/Evaluation Kits for PROFINET IO: DK Standard Ethernet Controller, Development/Evaluation Kits for PR
Initial Analysis by NIST1/11/2018 12:03:28 PM
Action
Type
Old Value
New Value
Added
CVSS V3
AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Added
CVSS V2
(AV:N/AC:L/Au:N/C:N/I:N/A:C)
Added
CWE
CWE-19
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:dk_standard_ethernet_controller_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:dk_standard_ethernet_controller:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:ek-ertec_200p_firmware:*:*:*:*:*:*:*:* versions up to (excluding) 4.5
OR
cpe:2.3:h:siemens:ek-ertec_200p:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:ek-ertec_200pn_io_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:ek-ertec_200pn_io:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_compact_field_unit_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_compact_field_unit:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200al_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200al:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200ecopn_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200ecopn:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200m_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200m:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200mp_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200mp:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200pro_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200pro:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200s_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200s:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_et_200sp_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_et_200sp:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_pn\/pn_coupler_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_pn\/pn_coupler:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-1200_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_s7-1200:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-1500_controller_firmware:2.0:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_s7-1500_controller:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-1500_firmware:*:*:*:*:*:*:*:* versions up to (excluding) 2.0
OR
cpe:2.3:h:siemens:simatic_s7-1500:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-200_firmware:*:*:*:*:*:*:*:* versions up to (excluding) 2.03.01
OR
cpe:2.3:h:siemens:simatic_s7-200:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-300_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_s7-300:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-400h_v6_firmware:*:*:*:*:*:*:*:* versions up to (excluding) 6.0.8
OR
cpe:2.3:h:siemens:simatic_s7-400h_v6:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-400pn\/dp_v7_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_s7-400pn\/dp_v7:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-400pn_v6_firmware:*:*:*:*:*:*:*:* versions up to (excluding) 6.0.6
OR
cpe:2.3:h:siemens:simatic_s7-400pn_v6:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_s7-410_v8_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_s7-410_v8:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simatic_winac_rtx_f_2010_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simatic_winac_rtx_f_2010:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simocode_pro_v_profinet_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:simocode_pro_v_profinet:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simotion_c_firmware:*:*:*:*:*:*:*:* versions up to (including) 5.1
OR
cpe:2.3:h:siemens:simotion_c:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simotion_d_firmware:*:*:*:*:*:*:*:* versions up to (including) 5.1
OR
cpe:2.3:h:siemens:simotion_d:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:simotion_p_firmware:*:*:*:*:*:*:*:* versions up to (including) 5.1
OR
cpe:2.3:h:siemens:simotion_p:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_dcm_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_dcm:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_dcp_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_dcp:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_g110m\/g120pn_firmware:*:*:*:*:*:*:*:* versions up to (including) 4.7
OR
cpe:2.3:h:siemens:sinamics_g110m\/g120pn:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_g130_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_g130:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_g150_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_g150:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_s110pn_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_s110pn:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_s120_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_s120:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_s150_v4.7_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_s150_v4.7:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_s150_v4.8_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_s150_v4.8:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinamics_v90pn_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinamics_v90pn:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sinumerik_840d_sl_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sinumerik_840d_sl:-:*:*:*:*:*:*:*
Added
CPE Configuration
AND
OR
*cpe:2.3:o:siemens:sirius_soft_starter_3rw44pn_firmware:-:*:*:*:*:*:*:*
OR
cpe:2.3:h:siemens:sirius_soft_starter_3rw44pn:-:*:*:*:*:*:*:*
Changed
Reference Type
http://www.securityfocus.com/bid/101964 No Types Assigned
http://www.securityfocus.com/bid/101964 Third Party Advisory, VDB Entry
Changed
Reference Type
https://www.siemens.com/cert/pool/cert/siemens_security_advisory_ssa-346262.pdf No Types Assigned