A vulnerability has been identified in SIMATIC S7-300 CPUs (All versions < V3.X.16). The affected CPUs improperly validate S7 communication packets which could cause a Denial-of-Service condition of the CPU. The CPU will remain in DEFECT mode until manual restart. Successful exploitation requires an attacker to be able to send a specially crafted S7 communication packet to a communication interface of the CPU. This includes Ethernet, PROFIBUS, and Multi Point Interfaces (MPI). No user interaction or privileges are required to exploit the security vulnerability. The vulnerability could allow causing a Denial-of-Service condition of the core functionality of the CPU, compromising the availability of the system. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

Source:  MITRE
View Analysis Description

Impact

CVSS v3.0 Severity and Metrics:

Base Score: 7.5 HIGH
Vector: AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H (V3 legend)
Impact Score: 3.6
Exploitability Score: 3.9


Attack Vector (AV): Network
Attack Complexity (AC): Low
Privileges Required (PR): None
User Interaction (UI): None
Scope (S): Unchanged
Confidentiality (C): None
Integrity (I): None
Availability (A): High

CVSS v2.0 Severity and Metrics:

Base Score: 7.8 HIGH
Vector: (AV:N/AC:L/Au:N/C:N/I:N/A:C) (V2 legend)
Impact Subscore: 6.9
Exploitability Subscore: 10.0


Access Vector (AV): Network
Access Complexity (AC): Low
Authentication (AU): None
Confidentiality (C): None
Integrity (I): None
Availability (A): Complete
Additional Information:
Allows disruption of service

References to Advisories, Solutions, and Tools

By selecting these links, you will be leaving NIST webspace. We have provided these links to other web sites because they may have information that would be of interest to you. No inferences should be drawn on account of other sites being referenced, or not, from this page. There may be other web sites that are more appropriate for your purpose. NIST does not necessarily endorse the views expressed, or concur with the facts presented on these sites. Further, NIST does not endorse any commercial products that may be mentioned on these sites. Please address comments about this page to nvd@nist.gov.

Hyperlink Resource
https://cert-portal.siemens.com/productcert/pdf/ssa-306710.pdf Vendor Advisory

Technical Details

Vulnerability Type (View All)

  • Resource Management Errors (CWE-399)

Known Affected Software Configurations Switch to CPE 2.2

Configuration 1 ( hide )
 cpe:2.3:o:siemens:simatic_s7-300_firmware:-:*:*:*:*:*:*:*
     Show Matching CPE(s)
Running on/with
 cpe:2.3:h:siemens:simatic_s7-300:-:*:*:*:*:*:*:*
     Show Matching CPE(s)

Configuration 2 ( hide )
 cpe:2.3:o:siemens:simatic_s7-300f_firmware:-:*:*:*:*:*:*:*
     Show Matching CPE(s)
Running on/with
 cpe:2.3:h:siemens:simatic_s7-300f:-:*:*:*:*:*:*:*
     Show Matching CPE(s)

Configuration 3 ( hide )
 cpe:2.3:o:siemens:simatic_s7-300fs_firmware:-:*:*:*:*:*:*:*
     Show Matching CPE(s)
Running on/with
 cpe:2.3:h:siemens:simatic_s7-300fs:-:*:*:*:*:*:*:*
     Show Matching CPE(s)

Configuration 4 ( hide )
 cpe:2.3:o:siemens:simatic_s7-300t_firmware:-:*:*:*:*:*:*:*
     Show Matching CPE(s)
Running on/with
 cpe:2.3:h:siemens:simatic_s7-300t:-:*:*:*:*:*:*:*
     Show Matching CPE(s)


Change History

1 change record found - show changes

Quick Info

CVE Dictionary Entry:
CVE-2018-16561
NVD Published Date:
04/17/2019
NVD Last Modified:
04/19/2019