Mitsubishi Electric Corporation AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:N
|
Added |
CWE |
|
Mitsubishi Electric Corporation CWE-287
|
Added |
Description |
|
Improper Authentication vulnerability in the mobile monitoring feature of ICONICS GENESIS64 versions 10.97 to 10.97.2, Mitsubishi Electric GENESIS64 versions 10.97 to 10.97.2 and Mitsubishi Electric MC Works64 all versions allows a remote unauthenticated attacker to bypass proper authentication and log in to the system when all of the following conditions are met: * Active Directory is used in the security setting.
* “Automatic log in” option is enabled in the security setting.
* The IcoAnyGlass IIS Application Pool is running under an Active Directory Domain Account.
* The IcoAnyGlass IIS Application Pool account is included in GENESIS64TM and MC Works64 Security and has permission to log in.
|
Added |
Reference |
|
Mitsubishi Electric Corporation https://jvn.jp/vu/JVNVU98894016/ [No types assigned]
|
Added |
Reference |
|
Mitsubishi Electric Corporation https://www.cisa.gov/news-events/ics-advisories/icsa-24-184-03 [No types assigned]
|
Added |
Reference |
|
Mitsubishi Electric Corporation https://www.mitsubishielectric.com/en/psirt/vulnerability/pdf/2024-004_en.pdf [No types assigned]
|