Vuln ID | Summary | CVSS Severity |
---|---|---|
CVE-2018-7762 |
A vulnerability exists in the web services to process SOAP requests in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow result in a buffer overflow. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 7.5 HIGH V2.0: 5.0 MEDIUM |
CVE-2018-7761 |
A vulnerability exists in the HTTP request parser in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200 which could allow arbitrary code execution. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2018-7760 |
An authorization bypass vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. Requests to CGI functions allow malicious users to bypass authorization. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2018-7759 |
A buffer overflow vulnerability exists in Schneider Electric's Modicon M340, Modicon Premium, Modicon Quantum PLC, BMXNOR0200. The buffer overflow vulnerability is caused by the length of the source string specified (instead of the buffer size) as the number of bytes to be copied. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 7.5 HIGH V2.0: 5.0 MEDIUM |
CVE-2018-7242 |
Vulnerable hash algorithms exists in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. The algorithm used to encrypt the password is vulnerable to hash collision attacks. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 9.8 CRITICAL V2.0: 5.0 MEDIUM |
CVE-2018-7241 |
Hard coded accounts exist in Schneider Electric's Modicon Premium, Modicon Quantum, Modicon M340, and BMXNOR0200 controllers in all versions of the communication modules. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 9.8 CRITICAL V2.0: 10.0 HIGH |
CVE-2018-7240 |
A vulnerability exists in Schneider Electric's Modicon Quantum in all versions of the communication modules which could allow arbitrary code execution. An FTP command used to upgrade the firmware of the module can be misused to cause a denial of service, or in extreme cases, to load a malicious firmware. Published: April 18, 2018; 4:29:00 PM -0400 |
V4.0:(not available) V3.0: 8.8 HIGH V2.0: 6.5 MEDIUM |