Search Parameters:
  • Keyword (text search): cpe:2.3:o:schneider-electric:modicon_m340_bmxp341000_firmware:2.8:*:*:*:*:*:*:*
  • CPE Name Search: true
There are 17 matching records.
Displaying matches 1 through 17.
Vuln ID Summary CVSS Severity
CVE-2021-22786

A CWE-200: Information Exposure vulnerability exists that could cause the exposure of sensitive information stored on the memory of the controller when communicating over the Modbus TCP protocol. Affected Products: Modicon M340 CPU (part numbers BMXP34*) (Versions prior to V3.30), Modicon M580 CPU (part numbers BMEP* and BMEH*) (Versions prior to SV3.20), Modicon MC80 (BMKC80) (Versions prior to V1.6), Modicon M580 CPU Safety (part numbers BMEP58*S and BMEH58*S) (All Versions), Modicon Momentum MDI (171CBU*) (Versions prior to V2.3), Legacy Modicon Quantum (All Versions)

Published: January 31, 2023; 11:15:08 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0:(not available)
CVE-2022-45789

A CWE-294: Authentication Bypass by Capture-replay vulnerability exists that could cause execution of unauthorized Modbus functions on the controller when hijacking an authenticated Modbus session. Affected Products: EcoStruxure Control Expert (All Versions), EcoStruxure Process Expert (All Versions), Modicon M340 CPU - part numbers BMXP34* (All Versions), Modicon M580 CPU - part numbers BMEP* and BMEH* (All Versions), Modicon M580 CPU Safety - part numbers BMEP58*S and BMEH58*S (All Versions)

Published: January 31, 2023; 1:15:07 AM -0500
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0:(not available)
CVE-2022-0222

A CWE-269: Improper Privilege Management vulnerability exists that could cause a denial of service of the Ethernet communication of the controller when sending a specific request over SNMP. Affected products: Modicon M340 CPUs(BMXP34* versions prior to V3.40), Modicon M340 X80 Ethernet Communication modules:BMXNOE0100 (H), BMXNOE0110 (H), BMXNOR0200H RTU(BMXNOE* all versions)(BMXNOR* versions prior to v1.7 IR24)

Published: November 22, 2022; 8:15:10 AM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0:(not available)
CVE-2022-37300

A CWE-640: Weak Password Recovery Mechanism for Forgotten Password vulnerability exists that could cause unauthorized access in read and write mode to the controller when communicating over Modbus. Affected Products: EcoStruxure Control Expert Including all Unity Pro versions (former name of EcoStruxure Control Expert) (V15.0 SP1 and prior), EcoStruxure Process Expert, Including all versions of EcoStruxure Hybrid DCS (former name of EcoStruxure Process Expert) (V2021 and prior), Modicon M340 CPU (part numbers BMXP34*) (V3.40 and prior), Modicon M580 CPU (part numbers BMEP* and BMEH*) (V3.20 and prior).

Published: September 12, 2022; 2:15:08 PM -0400
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0:(not available)
CVE-2021-22779

Authentication Bypass by Spoofing vulnerability exists in EcoStruxure Control Expert (all versions prior to V15.0 SP1, including all versions of Unity Pro), EcoStruxure Control Expert V15.0 SP1, EcoStruxure Process Expert (all versions, including all versions of EcoStruxure Hybrid DCS), SCADAPack RemoteConnect for x70 (all versions), Modicon M580 CPU (all versions - part numbers BMEP* and BMEH*), Modicon M340 CPU (all versions - part numbers BMXP34*), that could cause unauthorized access in read and write mode to the controller by spoofing the Modbus communication between the engineering software and the controller.

Published: July 14, 2021; 11:15:08 AM -0400
V4.0:(not available)
V3.1: 9.1 CRITICAL
V2.0: 6.4 MEDIUM
CVE-2020-7549

A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause denial of HTTP and FTP services when a series of specially crafted requests is sent to the controller over HTTP.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 5.3 MEDIUM
V2.0: 5.0 MEDIUM
CVE-2020-7543

A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2020-7542

A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2020-7541

A CWE-425: Direct Request ('Forced Browsing') vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of sensitive data when sending a specially crafted request to the controller over HTTP.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 5.3 MEDIUM
V2.0: 5.0 MEDIUM
CVE-2020-7540

A CWE-306: Missing Authentication for Critical Function vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause unauthenticated command execution in the controller when sending special HTTP requests.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0: 7.5 HIGH
CVE-2020-7539

A CWE-754 Improper Check for Unusual or Exceptional Conditions vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause a denial of service vulnerability when a specially crafted packet is sent to the controller over HTTP.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2020-7537

A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M580, Modicon M340, Legacy Controllers Modicon Quantum & Modicon Premium (see security notifications for affected versions), that could cause denial of service when a specially crafted Read Physical Memory request over Modbus is sent to the controller.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2020-7536

A CWE-754:Improper Check for Unusual or Exceptional Conditions vulnerability exists in Modicon M340 CPUs (BMXP34* versions prior to V3.30) Modicon M340 Communication Ethernet modules (BMXNOE0100 (H) versions prior to V3.4 BMXNOE0110 (H) versions prior to V6.6 BMXNOR0200H all versions), that could cause the device to be unreachable when modifying network parameters over SNMP.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 7.8 HIGH
CVE-2020-7535

A CWE-22: Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal' Vulnerability Type) vulnerability exists in the Web Server on Modicon M340, Legacy Offers Modicon Quantum and Modicon Premium and associated Communication Modules (see security notification for affected versions), that could cause disclosure of information when sending a specially crafted request to the controller over HTTP.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2020-7533

A CWE-255: Credentials Management vulnerability exists in Web Server on Modicon M340, Modicon Quantum and ModiconPremium Legacy offers and their Communication Modules (see security notification for version information) which could cause the execution of commands on the webserver without authentication when sending specially crafted HTTP requests.

Published: December 01, 2020; 10:15:12 AM -0500
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0: 7.5 HIGH
CVE-2019-6855

Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.

Published: January 06, 2020; 6:15:11 PM -0500
V4.0:(not available)
V3.1: 7.3 HIGH
V2.0: 7.5 HIGH
CVE-2017-6017

A Resource Exhaustion issue was discovered in Schneider Electric Modicon M340 PLC BMXNOC0401, BMXNOE0100, BMXNOE0110, BMXNOE0110H, BMXNOR0200H, BMXP341000, BMXP342000, BMXP3420102, BMXP3420102CL, BMXP342020, BMXP342020H, BMXP342030, BMXP3420302, BMXP3420302H, and BMXP342030H. A remote attacker could send a specially crafted set of packets to the PLC causing it to freeze, requiring the operator to physically press the reset button on the PLC in order to recover.

Published: June 29, 2017; 11:29:00 PM -0400
V4.0:(not available)
V3.0: 7.5 HIGH
V2.0: 7.8 HIGH