Vuln ID Summary CVSS Severity
CVE-2022-36325

Affected devices do not properly sanitize data introduced by an user when rendering the web interface. This could allow an authenticated remote attacker with administrative privileges to inject code and lead to a DOM-based XSS.

Published: August 10, 2022; 8:15:12 AM -0400
V4.0:(not available)
V3.1: 4.8 MEDIUM
V2.0:(not available)
CVE-2022-36324

Affected devices do not properly handle the renegotiation of SSL/TLS parameters. This could allow an unauthenticated remote attacker to bypass the TCP brute force prevention and lead to a denial of service condition for the duration of the attack.

Published: August 10, 2022; 8:15:12 AM -0400
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0:(not available)
CVE-2022-36323

Affected devices do not properly sanitize an input field. This could allow an authenticated remote attacker with administrative privileges to inject code or spawn a system root shell.

Published: August 10, 2022; 8:15:12 AM -0400
V4.0:(not available)
V3.1: 9.1 CRITICAL
V2.0:(not available)
CVE-2020-28400

Affected devices contain a vulnerability that allows an unauthenticated attacker to trigger a denial-of-service condition. The vulnerability can be triggered if a large amount of DCP reset packets are sent to the device.

Published: July 13, 2021; 7:15:08 AM -0400
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2019-13946

Profinet-IO (PNIO) stack versions prior V06.00 do not properly limit internal resource allocation when multiple legitimate diagnostic package requests are sent to the DCE-RPC interface. This could lead to a denial of service condition due to lack of memory for devices that include a vulnerable version of the stack. The security vulnerability could be exploited by an attacker with network access to an affected device. Successful exploitation requires no system privileges and no user interaction. An attacker could use the vulnerability to compromise the availability of the device.

Published: February 11, 2020; 11:15:15 AM -0500
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 7.8 HIGH
CVE-2018-5391

The Linux kernel, versions 3.9+, is vulnerable to a denial of service attack with low rates of specially modified packets targeting IP fragment re-assembly. An attacker may cause a denial of service condition by sending specially crafted IP fragments. Various vulnerabilities in IP fragmentation have been discovered and fixed over the years. The current vulnerability (CVE-2018-5391) became exploitable in the Linux kernel with the increase of the IP fragment reassembly queue size.

Published: September 06, 2018; 5:29:00 PM -0400
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 7.8 HIGH
CVE-2017-14491

Heap-based buffer overflow in dnsmasq before 2.78 allows remote attackers to cause a denial of service (crash) or execute arbitrary code via a crafted DNS response.

Published: October 03, 2017; 9:29:02 PM -0400
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0: 7.5 HIGH
CVE-2017-2681

Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. This vulnerability affects only SIMATIC HMI Multi Panels and HMI Mobile Panels, and S7-300/S7-400 devices.

Published: May 11, 2017; 6:29:00 AM -0400
V4.0:(not available)
V3.1: 6.5 MEDIUM
V2.0: 6.1 MEDIUM
CVE-2017-2680

Specially crafted PROFINET DCP broadcast packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). Human interaction is required to recover the systems. PROFIBUS interfaces are not affected.

Published: May 10, 2017; 9:29:05 PM -0400
V4.0:(not available)
V3.1: 6.5 MEDIUM
V2.0: 6.1 MEDIUM
CVE-2016-7090

The integrated web server on Siemens SCALANCE M-800 and S615 modules with firmware before 4.02 does not set the secure flag for the session cookie in an https session, which makes it easier for remote attackers to capture this cookie by intercepting its transmission within an http session.

Published: September 29, 2016; 6:59:03 AM -0400
V4.0:(not available)
V3.0: 4.0 MEDIUM
V2.0: 4.3 MEDIUM