CVE-2020-28220 |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in Modicon M258 Firmware (All versions prior to V5.0.4.11) and SoMachine/SoMachine Motion software (All versions), that could cause a buffer overflow when the length of a file transferred to the webserver is not verified. Published: December 10, 2020; 8:15:11 PM -0500 |
V4.0:(not available) V3.1: 6.8 MEDIUM V2.0: 5.2 MEDIUM |
CVE-2020-7488 |
A CWE-319: Cleartext Transmission of Sensitive Information vulnerability exists which could leak sensitive information transmitted between the software and the Modicon M218, M241, M251, and M258 controllers. Published: April 22, 2020; 3:15:11 PM -0400 |
V4.0:(not available) V3.1: 7.5 HIGH V2.0: 5.0 MEDIUM |
CVE-2020-7487 |
A CWE-345: Insufficient Verification of Data Authenticity vulnerability exists which could allow the attacker to execute malicious code on the Modicon M218, M241, M251, and M258 controllers. Published: April 22, 2020; 3:15:11 PM -0400 |
V4.0:(not available) V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2017-7574 |
Schneider Electric SoMachine Basic 1.4 SP1 and Schneider Electric Modicon TM221CE16R 1.3.3.3 devices have a hardcoded-key vulnerability. The Project Protection feature is used to prevent unauthorized users from opening an XML protected project file, by prompting the user for a password. This XML file is AES-CBC encrypted; however, the key used for encryption (SoMachineBasicSoMachineBasicSoMa) cannot be changed. After decrypting the XML file with this key, the user password can be found in the decrypted data. After reading the user password, the project can be opened and modified with the Schneider product. Published: April 06, 2017; 5:59:00 PM -0400 |
V4.0:(not available) V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2013-0662 |
Multiple stack-based buffer overflows in ModbusDrv.exe in Schneider Electric Modbus Serial Driver 1.10 through 3.2 allow remote attackers to execute arbitrary code via a large buffer-size value in a Modbus Application Header. Published: April 01, 2014; 2:17:08 AM -0400 |