U.S. flag   An official website of the United States government
Dot gov

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Https

Secure .gov websites use HTTPS
A lock (Dot gov) or https:// means you've safely connected to the .gov website. Share sensitive information only on official, secure websites.

Search Results (Refine Search)

Search Parameters:
  • Results Type: Overview
  • Keyword (text search): cpe:2.3:a:schneider-electric:unity_pro:7.0:*:*:*:*:*:*:*
  • CPE Name Search: true
There are 5 matching records.
Displaying matches 1 through 5.
Vuln ID Summary CVSS Severity
CVE-2020-7560

A CWE-123: Write-what-where Condition vulnerability exists in EcoStruxure™ Control Expert (all versions) and Unity Pro (former name of EcoStruxure™ Control Expert) (all versions), that could cause a crash of the software or unexpected code execution when opening a malicious file in EcoStruxure™ Control Expert software.

Published: December 10, 2020; 8:15:12 PM -0500
V4.0:(not available)
V3.1: 8.6 HIGH
V2.0: 6.8 MEDIUM
CVE-2020-7475

A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection'), reflective DLL, vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20), Modicon M580 (all versions prior to V3.10), which, if exploited, could allow attackers to transfer malicious code to the controller.

Published: March 23, 2020; 3:15:12 PM -0400
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0: 7.5 HIGH
CVE-2019-6855

Incorrect Authorization vulnerability exists in EcoStruxure Control Expert (all versions prior to 14.1 Hot Fix), Unity Pro (all versions), Modicon M340 (all versions prior to V3.20) , and Modicon M580 (all versions prior to V3.10), which could cause a bypass of the authentication process between EcoStruxure Control Expert and the M340 and M580 controllers.

Published: January 06, 2020; 6:15:11 PM -0500
V4.0:(not available)
V3.1: 7.3 HIGH
V2.0: 7.5 HIGH
CVE-2016-8354

An issue was discovered in Schneider Electric Unity PRO prior to V11.1. Unity projects can be compiled as x86 instructions and loaded onto the PLC Simulator delivered with Unity PRO. These x86 instructions are subsequently executed directly by the simulator. A specially crafted patched Unity project file can make the simulator execute malicious code by redirecting the control flow of these instructions.

Published: February 13, 2017; 4:59:00 PM -0500
V4.0:(not available)
V3.0: 7.0 HIGH
V2.0: 5.1 MEDIUM
CVE-2013-0662

Multiple stack-based buffer overflows in ModbusDrv.exe in Schneider Electric Modbus Serial Driver 1.10 through 3.2 allow remote attackers to execute arbitrary code via a large buffer-size value in a Modbus Application Header.

Published: April 01, 2014; 2:17:08 AM -0400
V4.0:(not available)
V3.x:(not available)
V2.0: 9.3 HIGH