U.S. flag   An official website of the United States government
Dot gov

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

Https

Secure .gov websites use HTTPS
A lock (Dot gov) or https:// means you've safely connected to the .gov website. Share sensitive information only on official, secure websites.

Search Results (Refine Search)

Search Parameters:
  • Results Type: Overview
  • Keyword (text search): cpe:2.3:o:omron:nj501-1320_firmware:-:*:*:*:*:*:*:*
  • CPE Name Search: true
There are 6 matching records.
Displaying matches 1 through 6.
Vuln ID Summary CVSS Severity
CVE-2024-33687

Insufficient verification of data authenticity issue exists in NJ Series CPU Unit all versions and NX Series CPU Unit all versions. If a user program in the affected product is altered, the product may not be able to detect the alteration.

Published: June 24, 2024; 11:15:11 AM -0400
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0:(not available)
CVE-2023-27396

FINS (Factory Interface Network Service) is a message communication protocol, which is designed to be used in closed FA (Factory Automation) networks, and is used in FA networks composed of OMRON products. Multiple OMRON products that implement FINS protocol contain following security issues -- (1)Plaintext communication, and (2)No authentication required. When FINS messages are intercepted, the contents may be retrieved. When arbitrary FINS messages are injected, any commands may be executed on, or the system information may be retrieved from, the affected device. Affected products and versions are as follows: SYSMAC CS-series CPU Units, all versions, SYSMAC CJ-series CPU Units, all versions, SYSMAC CP-series CPU Units, all versions, SYSMAC NJ-series CPU Units, all versions, SYSMAC NX1P-series CPU Units, all versions, SYSMAC NX102-series CPU Units, all versions, and SYSMAC NX7 Database Connection CPU Units (Ver.1.16 or later)

Published: June 19, 2023; 1:15:09 AM -0400
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0:(not available)
CVE-2022-31206

The Omron SYSMAC Nx product family PLCs (NJ series, NY series, NX series, and PMAC series) through 2022-005-18 lack cryptographic authentication. These PLCs are programmed using the SYMAC Studio engineering software (which compiles IEC 61131-3 conformant POU code to native machine code for execution by the PLC's runtime). The resulting machine code is executed by a runtime, typically controlled by a real-time operating system. The logic that is downloaded to the PLC does not seem to be cryptographically authenticated, allowing an attacker to manipulate transmitted object code to the PLC and execute arbitrary machine code on the processor of the PLC's CPU module in the context of the runtime. In the case of at least the NJ series, an RTOS and hardware combination is used that would potentially allow for memory protection and privilege separation and thus limit the impact of code execution. However, it was not confirmed whether these sufficiently segment the runtime from the rest of the RTOS.

Published: July 26, 2022; 6:15:11 PM -0400
V4.0:(not available)
V3.1: 9.8 CRITICAL
V2.0:(not available)
CVE-2022-34151

Use of hard-coded credentials vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who successfully obtained the user credentials by analyzing the affected product to access the controller.

Published: July 03, 2022; 10:15:07 PM -0400
V4.0:(not available)
V3.1: 8.1 HIGH
V2.0: 6.8 MEDIUM
CVE-2022-33971

Authentication bypass by capture-replay vulnerability exists in Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, and Machine automation controller NJ series all models V 1.48 and earlier, which may allow an adjacent attacker who can analyze the communication between the controller and the specific software used by OMRON internally to cause a denial-of-service (DoS) condition or execute a malicious program.

Published: July 03, 2022; 10:15:07 PM -0400
V4.0:(not available)
V3.1: 7.5 HIGH
V2.0: 5.4 MEDIUM
CVE-2022-33208

Authentication bypass by capture-replay vulnerability exists in Machine automation controller NJ series all models V 1.48 and earlier, Machine automation controller NX7 series all models V1.28 and earlier, Machine automation controller NX1 series all models V1.48 and earlier, Automation software 'Sysmac Studio' all models V1.49 and earlier, and Programmable Terminal (PT) NA series NA5-15W/NA5-12W/NA5-9W/NA5-7W models Runtime V1.15 and earlier, which may allow a remote attacker who can analyze the communication between the affected controller and automation software 'Sysmac Studio' and/or a Programmable Terminal (PT) to access the controller.

Published: July 03, 2022; 10:15:07 PM -0400
V4.0:(not available)
V3.1: 8.1 HIGH
V2.0: 6.8 MEDIUM