Vuln ID Summary CVSS Severity
CVE-2021-42797

Path traversal vulnerability in AVEVA Edge (formerly InduSoft Web Studio) versions R2020 and prior allows an unauthenticated user to steal the Windows access token of the user account configured for accessing external DB resources.

Published: December 15, 2023; 8:15:07 PM -0500
V3.1: 7.5 HIGH
V2.0:(not available)
CVE-2021-42796

An issue was discovered in ExecuteCommand() in AVEVA Edge (formerly InduSoft Web Studio) versions R2020 and prior that allows unauthenticated arbitrary commands to be executed.

Published: December 15, 2023; 8:15:07 PM -0500
V3.1: 9.8 CRITICAL
V2.0:(not available)
CVE-2021-42794

An issue was discovered in AVEVA Edge (formerly InduSoft Web Studio) versions R2020 and prior. The application allows a client to provide a malicious connection string that could allow an adversary to port scan the LAN, depending on the hosts' responses.

Published: December 15, 2023; 8:15:07 PM -0500
V3.1: 5.3 MEDIUM
V2.0:(not available)
CVE-2019-6545

AVEVA Software, LLC InduSoft Web Studio prior to Version 8.1 SP3 and InTouch Edge HMI (formerly InTouch Machine Edition) prior to Version 2017 Update. An unauthenticated remote user could use a specially crafted database connection configuration file to execute an arbitrary process on the server machine.

Published: February 12, 2019; 8:29:00 PM -0500
V3.1: 7.5 HIGH
V2.0: 5.0 MEDIUM
CVE-2019-6543

AVEVA Software, LLC InduSoft Web Studio prior to Version 8.1 SP3 and InTouch Edge HMI (formerly InTouch Machine Edition) prior to Version 2017 Update. Code is executed under the program runtime privileges, which could lead to the compromise of the machine.

Published: February 12, 2019; 8:29:00 PM -0500
V3.1: 9.8 CRITICAL
V2.0: 10.0 HIGH
CVE-2018-17916

InduSoft Web Studio versions prior to 8.1 SP2, and InTouch Edge HMI (formerly InTouch Machine Edition) versions prior to 2017 SP2. A remote attacker could send a carefully crafted packet to exploit a stack-based buffer overflow vulnerability during tag, alarm, or event related actions such as read and write, with potential for code to be executed. If InduSoft Web Studio remote communication security was not enabled, or a password was left blank, a remote user could send a carefully crafted packet to invoke an arbitrary process, with potential for code to be executed. The code would be executed under the privileges of the InduSoft Web Studio or InTouch Edge HMI runtime and could lead to a compromise of the InduSoft Web Studio or InTouch Edge HMI server machine.

Published: November 02, 2018; 9:29:00 AM -0400
V3.1: 9.8 CRITICAL
V2.0: 10.0 HIGH
CVE-2018-17914

InduSoft Web Studio versions prior to 8.1 SP2, and InTouch Edge HMI (formerly InTouch Machine Edition) versions prior to 2017 SP2. This vulnerability could allow an unauthenticated user to remotely execute code with the same privileges as that of the InduSoft Web Studio or InTouch Edge HMI (formerly InTouch Machine Edition) runtime.

Published: November 02, 2018; 9:29:00 AM -0400
V3.1: 9.8 CRITICAL
V2.0: 10.0 HIGH
CVE-2018-10620

AVEVA InduSoft Web Studio v8.1 and v8.1SP1, and InTouch Machine Edition v2017 8.1 and v2017 8.1 SP1 a remote user could send a carefully crafted packet to exploit a stack-based buffer overflow vulnerability during tag, alarm, or event related actions such as read and write, with potential for code to be executed.

Published: July 19, 2018; 3:29:00 PM -0400
V3.1: 9.8 CRITICAL
V2.0: 7.5 HIGH
CVE-2018-8840

A remote attacker could send a carefully crafted packet in InduSoft Web Studio v8.1 and prior versions, and/or InTouch Machine Edition 2017 v8.1 and prior versions during a tag, alarm, or event related action such as read and write, which may allow remote code execution.

Published: April 18, 2018; 4:29:00 PM -0400
V3.0: 9.8 CRITICAL
V2.0: 10.0 HIGH
CVE-2017-14024

A Stack-based Buffer Overflow issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 Patch 1 and prior versions, and InTouch Machine Edition v8.0 SP2 Patch 1 and prior versions. The stack-based buffer overflow vulnerability has been identified, which may allow remote code execution with high privileges.

Published: November 13, 2017; 3:29:00 PM -0500
V3.0: 9.8 CRITICAL
V2.0: 10.0 HIGH
CVE-2017-13997

A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.

Published: October 02, 2017; 9:29:01 PM -0400
V3.0: 9.8 CRITICAL
V2.0: 10.0 HIGH
CVE-2017-7968

An Incorrect Default Permissions issue was discovered in Schneider Electric Wonderware InduSoft Web Studio v8.0 Patch 3 and prior versions. Upon installation, Wonderware InduSoft Web Studio creates a new directory and two files, which are placed in the system's path and can be manipulated by non-administrators. This could allow an authenticated user to escalate his or her privileges.

Published: May 19, 2017; 11:29:00 AM -0400
V3.0: 7.8 HIGH
V2.0: 7.2 HIGH
CVE-2015-7375

Schneider Electric InduSoft Web Studio before 8.0 allows remote attackers to execute arbitrary code or cause a denial of service (unhandled runtime exception and application crash) via a crafted Indusoft Project file.

Published: September 25, 2015; 10:59:01 AM -0400
V3.x:(not available)
V2.0: 7.5 HIGH
CVE-2015-7374

The Remote Agent component in Schneider Electric InduSoft Web Studio before 8.0 allows remote attackers to execute arbitrary code via unspecified vectors, aka ZDI-CAN-2649.

Published: September 25, 2015; 10:59:00 AM -0400
V3.x:(not available)
V2.0: 7.5 HIGH
CVE-2015-1009

Schneider Electric InduSoft Web Studio before 7.1.3.5 Patch 5 and Wonderware InTouch Machine Edition through 7.1 SP3 Patch 4 use cleartext for project-window password storage, which allows local users to obtain sensitive information by reading a file.

Published: July 31, 2015; 9:59:00 PM -0400
V3.x:(not available)
V2.0: 1.7 LOW
CVE-2015-0999

Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 store cleartext OPC User credentials in a configuration file, which allows local users to obtain sensitive information by reading this file.

Published: March 29, 2015; 6:59:08 AM -0400
V3.x:(not available)
V2.0: 2.1 LOW
CVE-2015-0998

Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 transmit cleartext credentials, which allows remote attackers to obtain sensitive information by sniffing the network.

Published: March 29, 2015; 6:59:07 AM -0400
V3.x:(not available)
V2.0: 3.3 LOW
CVE-2015-0997

Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 provide an HMI user interface that lists all valid usernames, which makes it easier for remote attackers to obtain access via a brute-force password-guessing attack.

Published: March 29, 2015; 6:59:06 AM -0400
V3.x:(not available)
V2.0: 5.0 MEDIUM
CVE-2015-0996

Schneider Electric InduSoft Web Studio before 7.1.3.4 SP3 Patch 4 and InTouch Machine Edition 2014 before 7.1.3.4 SP3 Patch 4 rely on a hardcoded cleartext password to control read access to Project files and Project Configuration files, which makes it easier for local users to obtain sensitive information by discovering this password.

Published: March 29, 2015; 6:59:05 AM -0400
V3.x:(not available)
V2.0: 2.1 LOW
CVE-2014-0780

Directory traversal vulnerability in NTWebServer in InduSoft Web Studio 7.1 before SP2 Patch 4 allows remote attackers to read administrative passwords in APP files, and consequently execute arbitrary code, via unspecified web requests.

Published: April 25, 2014; 1:12:07 AM -0400
V3.x:(not available)
V2.0: 7.5 HIGH