Search Results (Refine Search)
- Results Type: Overview
- Keyword (text search): cpe:2.3:h:rockwellautomation:guardlogix_5580:-:*:*:*:*:*:*:*
- CPE Name Search: true
Vuln ID | Summary | CVSS Severity |
---|---|---|
CVE-2022-3752 |
An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation. Published: December 19, 2022; 6:15:10 PM -0500 |
V3.1: 7.5 HIGH V2.0:(not available) |
CVE-2020-6998 |
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products. Published: July 27, 2022; 5:15:08 PM -0400 |
V3.1: 8.6 HIGH V2.0:(not available) |
CVE-2022-1797 |
A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. Published: June 02, 2022; 10:15:33 AM -0400 |
V3.1: 8.6 HIGH V2.0: 7.8 HIGH |
CVE-2022-1161 |
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. Published: April 11, 2022; 4:15:18 PM -0400 |
V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |
CVE-2022-1159 |
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user. Published: April 01, 2022; 7:15:12 PM -0400 |
V3.1: 7.2 HIGH V2.0: 6.5 MEDIUM |
CVE-2021-22681 |
Rockwell Automation Studio 5000 Logix Designer Versions 21 and later, and RSLogix 5000 Versions 16 through 20 use a key to verify Logix controllers are communicating with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Rockwell Automation Studio 5000 Logix Designer Versions 21 and later and RSLogix 5000: Versions 16 through 20 are vulnerable because an unauthenticated attacker could bypass this verification mechanism and authenticate with Rockwell Automation CompactLogix 1768, 1769, 5370, 5380, 5480: ControlLogix 5550, 5560, 5570, 5580; DriveLogix 5560, 5730, 1794-L34; Compact GuardLogix 5370, 5380; GuardLogix 5570, 5580; SoftLogix 5800. Published: March 03, 2021; 1:15:14 PM -0500 |
V3.1: 9.8 CRITICAL V2.0: 7.5 HIGH |